Purpose, Function
The generator operates by obtaining drive force from the engine via the drive belt and generates the required electricity for electronic devices.
Construction
The generator is installed on the engine left front side.

Output control is performed by the PCM resulting in the elimination of the IC regulator and the simplification of the construction.
Two delta connection type stator coils have been adopted.


The two stator coils form the circuit having a phase difference, and magnetic pull, which operates between the rotor and stator coil by the phase difference, is theoretically eliminated. Due to this, electromagnetic vibration and generator operation noise (electromagnetic noise) have been reduced.

Pulsation occurring through voltage rectifying using two stator coils having a phase difference is minimized and stable voltage output is supplied.

Operation
For generator control details, refer to CONTROL SYSTEM..
Fail-safe
Function not equipped.
Generator Removal/Installation [Skyactiv G 2.0]
Refrigerant ChargingClutch Pedal Position (CPP) Switch Inspection [Skyactiv G 2.0]
Continuity Inspection
1. Verify that the CPP switch is installed properly..
2. Disconnect the negative battery cable..
3. Disconnect the CPP switch connector.
4. Verify that the continuity between CPP switch terminals A and B when the clutch
pedal is depressed and when it is released is acc ...
Hydraulic Variable Valve Timing Actuator
Purpose, Function
The hydraulic variable valve timing actuator operates according to the hydraulic
pressure and changes the phases of the exhaust camshaft. As a result, the open/close
period of the exhaust valve is changed, optimized valve timing in accordance
with driving conditions ...
Refrigerant Charging
CAUTION:
Do not use a different type of refrigerant or charge beyond the specified
level. Otherwise, cooling ability will be lowered and the A/C compressor could
be damaged.
Charging Recycled HFC-134a Refrigerant
1. Connect an HFC-134a recovery/recycling/recharging device to the ...