Purpose, Function
The generator operates by obtaining drive force from the engine via the drive belt and generates the required electricity for electronic devices.
Construction
The generator is installed on the engine left front side.

Output control is performed by the PCM resulting in the elimination of the IC regulator and the simplification of the construction.
Two delta connection type stator coils have been adopted.


The two stator coils form the circuit having a phase difference, and magnetic pull, which operates between the rotor and stator coil by the phase difference, is theoretically eliminated. Due to this, electromagnetic vibration and generator operation noise (electromagnetic noise) have been reduced.

Pulsation occurring through voltage rectifying using two stator coils having a phase difference is minimized and stable voltage output is supplied.

Operation
For generator control details, refer to CONTROL SYSTEM..
Fail-safe
Function not equipped.
Generator Removal/Installation [Skyactiv G 2.0]
Refrigerant ChargingMap Light Inspection
Front Map Light
1. Disconnect the negative battery cable..
2. Remove the front map light..
3. Verify that the continuity between the front map light terminals is as indicated
in the table.
If not as indicated in the table, replace the front map light or front map
light bulb ...
Upper Panel Removal/Installation
1. Disconnect the negative battery cable..
2. Remove the following parts:
a. Front console box.
b. Shift lever knob (MTX).
c. Shift panel.
3. Open the console lid.
4. Remove the button, then open the fastener.
5. Take the shaded area shown in the figure, and remove the upper panel ...
Canister Vent (Cv) Solenoid Valve Inspection
U.S.A. And CANADA
Airflow inspection
1. Disconnect the negative battery cable..
2. Remove the CV solenoid valve..
3. Inspect airflow between the ports under the following conditions.
Measured condition
Continuity between A—B
When volta ...