U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Do not operate CV solenoid valve.
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 1.8 kPa {14 mmHg, 0.53 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 2.0 kPa {15 mmHg, 0.59 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Except U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Catch Tank
Charcoal Canister Removal/InstallationFuel Distributor
Purpose, Function
Distributes fuel pumped from the high pressure fuel pump to each fuel injector.
Construction
The fuel distributor is installed to the cylinder head.
The fuel distributor is integrated with the fuel pressure sensor.
...
Main Relay Control [Skyactiv G 2.0]
Outline
Supplies power to each part by switching the main relay on/off at the optimal
timing according to the vehicle conditions.
Block Diagram
Operation
When the ignition is switched ON, the main relay turns on and electrical
power is supplied to each sensor and devic ...
Clock Spring Inspection [Two Step Deployment Control System]
1. Disconnect the negative battery cable and wait for 1 min or more..
2. Remove the driver?side air bag module..
3. Remove the steering wheel..
4. Remove the column cover..
5. Remove the clock spring..
6. Verify that the continuity is as indicated in the table.
If not as indicated ...