U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Do not operate CV solenoid valve.
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 1.8 kPa {14 mmHg, 0.53 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 2.0 kPa {15 mmHg, 0.59 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Except U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Catch Tank
Charcoal Canister Removal/InstallationAmbient Temperature Sensor [Manual Air Conditioner]
Purpose
The ambient temperature sensor detects the ambient temperature.
Function
The ambient temperature sensor converts the detected temperature to an electric
signal.
Construction
A thermistor-type ambient temperature sensor has been adopted.
The ambient ...
Instrument Cluster Disassembly/Assembly
CAUTION:
If the instrument cluster is hit forcefully during disassembly such as by
being dropped, it could get damaged and the system may not operate normally.
When disassembling the instrument cluster, perform the procedure on a workbench
on clean clothes being careful not to drop ...
Oil Jet Valve
Purpose, Function
The oil jet valve injects engine oil on the back of the piston to cool the
piston.
Construction
The oil jet valve is installed into the cylinder block.
The oil jet valve is built into the check ball and spring.
Operation
1. When ...