U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Do not operate CV solenoid valve.
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 1.8 kPa {14 mmHg, 0.53 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 2.0 kPa {15 mmHg, 0.59 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Except U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Catch Tank
Charcoal Canister Removal/InstallationVacuum Pump [Skyactiv G 2.0]
Purpose, Function
Ensures vacuum required for braking force to compensate for the decrease
in intake manifold vacuum applied to the power brake unit caused by the retard
intake valve closing.
Construction
The vacuum pump is installed to the rear housing.
For s ...
Starter Interlock Switch Inspection [Skyactiv G 2.0]
CAUTION:
Do not reuse the starter interlock switch if it is removed from the vehicle
even once. Replace with a new starter interlock switch when installing.
1. Disconnect the negative battery cable..
2. Disconnect the starter interlock switch connector.
3. Verify that the contin ...
Relay And Fuse Block Middle Cover Disassembly/Assembly
1. Insert a tape-wrapped flathead screwdriver into the service hole in the position
shown in the figure.
2. While pressing the relay and fuse block middle cover tab in the direction
of arrow (1) shown in the figure, pull out the bracket in the direction of arrow
(2) to detach the relay a ...