U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Do not operate CV solenoid valve.
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 1.8 kPa {14 mmHg, 0.53 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 2.0 kPa {15 mmHg, 0.59 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Except U.S.A. And CANADA
Leakage inspection
1. Perform the following procedures:
Assemble the hose used for inspection to port A.
Cover ports B and C with the caps.

CAUTION:
Do not apply a pressure 20 kPa {150 mmHg, 5.91 inHg} or more to the charcoal canister for 1 min. or more. Doing so will damage the charcoal canister.
2. Apply pressure (19.6 kPa {147 mmHg, 5.79 inHg}
) through the hose, and verify that air does not leak from the charcoal canister.

If there is airflow, replace the charcoal canister..
If there is no airflow, perform the following “Airflow Inspection”..
Airflow inspection
1. Perform the following procedure to verify the charcoal canister airflow.
Plug the port B.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port A.
Verify that there is airflow from port C.
If there is no airflow, replace the charcoal canister..
Plug the port A.

Apply a pressure of 0.98 kPa {7.4 mmHg, 0.29 inHg}
to port C.
Verify that there is airflow from port B.
If there is no airflow, replace the charcoal canister..
Catch Tank
Charcoal Canister Removal/InstallationHydraulic Variable Valve Timing Actuator
Purpose, Function
The hydraulic variable valve timing actuator operates according to the hydraulic
pressure and changes the phases of the exhaust camshaft. As a result, the open/close
period of the exhaust valve is changed, optimized valve timing in accordance
with driving conditions ...
Front Body Control Module (Fbcm) Inspection
1. Remove the fuse box cover..
2. Remove the front body control module (FBCM) from the fuse box..
3. Verify that the voltages of each of the terminals are as indicated in the
Terminal Voltage Table (Reference).
If the voltage is not as indicated in the table, inspect the parts under
...
Front ABS Wheel Speed Sensor Inspection
Sensor Output Value Inspection
CAUTION:
Resistance inspection using other testers may cause damage to the ABS wheel-speed
sensor internal circuit. Be sure to use the M-MDS to inspect the ABS wheel-speed
sensor.
1. Switch the ignition to off.
2. Connect the M-MDS to the DLC-2. ...